Diamante Pro™ High-Wall Series
Pioneer® Diamante Pro™ 12,000 BTU 20 SEER2 115V High-Wall Ductless Mini-Split Air Conditioner Inverter Heat Pump with 16 Ft. Kit
Pioneer® Diamante Pro™ 12,000 BTU 20 SEER2 115V High-Wall Ductless Mini-Split Air Conditioner Inverter Heat Pump with 16 Ft. Kit
-
Estimated delivery if ordered today: Dec 10 - Dec 14
Couldn't load pickup availability
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Why buy from our store?
Your Purchase Includes:
Outdoor Condenser
Pre-charged from the factory with enough R454-B refrigerant to accomodate up to 25' lineset lengths, and equipped with intelligent self-defrost.
Indoor Air Handler
Whisper-silent and beautifully sleek, it mounts onto the wall and features a washable, re-usable dust filter and an easy-to-use self-clean mode for easy maintenance.
16' Installation Kit
Included with system purchase is the full installation kit which features a 16' insulated copper lineset, 16' signal cable between units, and a 10' drain hose.
Handheld Remote
Functional in form and easy-to-read, the remote offers all of the essential features like Cool, Heat, Dry and Fan modes, as well as I FEEL to detect nearby temperature.
Summary
- High Efficiency Diamante Pro™ Ductless Mini Split Heat Pump System
- Cooling capacity: 12,000 BTU/H with 20.0 SEER2 / 10.5 EER2 efficiency
- Heating capacity: 12,000 BTU/H with 9.5 HSPF2 / 3.41 COP2 efficiency
- Voltage: 110/120V, 60Hz, 1Ph
- High Wall-Mounted Ductless Air Conditioning & Heating System
- Variable-Speed DC Inverter Driven Performance
- Factory-Precharged with Environmentally Friendly R454b Refrigerant
- Low Ambient Range Operation (As low as -4°F in Heating / As high as 122°F in Cooling)
Features
- Heat Pump with Cooling, Heating, Dry, and Ventilation Modes
- Dual-Drainage Ports
- Washable, Reusable Air Filters
- Dual-Axis Airflow (Motorized Up-Down and Left-Right Louvers)
- Functional Remote with:
- ECO and SLEEP Modes, for Energy-Conservation
- Timer On/Off Control
- TURBO, for Times of High-Demand
- Self-Clean Cycle
- MEMORY, to Recall Favorite Settings
- IFEEL, to Detect and Adjust to Local Temperature
Technical Information & Performance
-
System Kit
- Power Supply: 110~120V, 60Hz, 1Ph
- Cooling Rated Capacity: 12,000 BTU/h
- Cooling Capacity Range: 3,400~13,000 BTU/h
- Cooling SEER2: 20.0 BTU/W.h
- Cooling EER2: 10.5 BTU/W.h
- Heating Rated Capacity: 12,000 BTU/h
- Heating Capacity Range: 3,400~13,900 BTU/h
- Heating HSPF2 (Region IV): 9.5 BTU/W.h
- Heating C.O.P.2 (47°F/5°F): 3.41 / 1.8 W/W
- Refrigerant Type: R454b
- Recommended Room Size: 200~500 sq ft
- Minimum Room Size: 34 sq ft
- Minimum Installation Height: 6 ft
- Piping Diameter: 1/4 x 3/8"
- AHRI Reference: 217048742
-
Indoor Unit
- Part Number: WT012ALSI20HLF
- Air Flow (Turbo/Hi/Med/Lo/Mute): 342 / 270 / 235 / 200 / 152 CFM
- Sound Level (Turbo/Hi/Med/Lo/Mute): 45 / 42 / 35 / 30 / 28 dB(A)
- Product Dimensions (WDH): 31"-7/8 x 8" x 11"-1/2 Inches
- Carton Dimensions (WDH): 34"-7/8 x 10"-3/4 x 14"-3/8 Inches
- Net / Gross Weight: 19.8 / 26.5 lbs.
-
Outdoor Unit
- Part Number: YN012ALSI20RPF
- Breaker Needed: 20A (single-pole)
- Sound Level: 55 dB(A)
- Net Dimensions (WDH): 31" x 11"-1/2 x 19"-3/8 Inches
- Carton Dimensions (WDH): 33" x 13"-3/8 x 22"-3/4 Inches
- Net / Gross Weight: 55.1 / 66.1 lbs
Dimension Chart
Diamante Pro™ High-Wall Series
Questions & Answers
Have a Question?
-
What are the running amps or watts of this unit 12k btu for both heat and AC modes?
Cooling: 1050W / Heating: 1030W - Current (Cooling): 9.5A / Current (Heating): 9.3A
See full info here: https://www.pdhvac.com/site/dl/wyt20/WYT20-BROC-2501.pdf
-
What size is the drain line??
The drain line is 5/8" OD.
-
How much current does this unit draw?
Rated Current (Cooling/Heating at full 12K BTU Capacity): 9.5 / 9.3 amps
-
How far apart are the feet center to center?
Regarding the outdoor unit, the mounting feet are 16-3/8" apart. For more info please see page 53 here: https://www.pdhvac.com/site/dl/wyt20/WYT20-IMUM-2501.pdf
-
Can you attach the air hose line of the inside unit to the top, bottom or sides? We cannot connect it to the backside of the unit.
A left or right side exit is feasible. Options #1 and #3 on page 36 of the installation manual show this being done: https://www.pdhvac.com/site/dl/wyt20/WYT20-IMUM-2501.pdf